  • 1 явление дугообразования

    Solar energy: arcing phenomenon

    Универсальный русско-английский словарь > явление дугообразования

  • 2 НКУ с устройствами ограничения воздействия внутренней дуги

    1. assembly equipped with devices limiting internal arc effects

     

    НКУ с устройствами ограничения воздействия внутренней дуги
    -
    [Интент]

    Параллельные тексты EN-RU

    Assemblies equipped with devices limiting internal arc effects (active protection)

    A design philosophy which is completely different from that just considered consists in guaranteeing the resistance to internal arcing by installing devices limiting the arc.

    The approaches in that direction can be of two different types:
    • limiting the destructive effects of the arc, once it has occured, by means of arc detectors
    • limiting the destructive effects of the arc, once it has occured, by means of overpressure detectors.

    The first possibility consists in installing in the assembly arc detectors which sense the light flux associated with the electric arc phenomenon.

    Once the arc has been detected, these devices send an opening signal to the incoming circuit-breaker, thus guaranteeing tripping times of the order of 1-2 ms, therefore shorter than those proper of the circuit-breaker.

    The operating logic of an arc detector is the following: the occurrence of an arc inside the switchboard is detected by the arc detector because an intense light radiation is associated with this phenomenon.

    The arcing control system detects the event and sends a tripping signal to the circuit-breaker.

    All the above with trip times of a few milliseconds and supplanting the tripping of the CB overcurrent relay which, for example, could be delayed due to current selectivity questions.

    Figure 1 shows the possible positions where this device can be installed inside a switchboard.

    The ideal solution is that which provides the installation of at least one detector for each column, with the consequent reduction to a minimum of the length of the optical fibers carrying the signal.

    In order to prevent from an unwanted tripping caused by light sources indepent of the arc (lamps, solar radiation etc.), an additional current sensor is often positioned at the incoming of the main circuit-breaker.

    Only in the event of an arc, both the incoming sensor which detects an “anomalous” current due to the arc fault as well as the sensor detecting the light radiation as sociated with the arc enable the system to intervene and allow the consequent opening of the circuit-breaker.

    The second possibility consists in installing overpressure sensors inside the switchboard.

    As previously described, the overpressure wave is one of the other effects occurring inside an assembly in case of arcing.

    As a consequence it is possible to install some pressure sensors which are able to signal the pressure peak associated with the arc ignition with a delay of about 10-15 ms.

    The signal operates on the supply circuit-breaker without waiting for the trip times of the selectivity protections to elapse, which are necessarily longer.

    Such a system does not need any electronic processing device, since it acts directly on the tripping coil of the supply circuit-breaker.

    Obviously it is essential that the device is set at fixed trip thresholds.

    When an established internal overpressure is reached, the arc detector intervenes.

    However, it is not easy to define in advance the value of overpressure generated by an arc fault inside a switchboard.

    [ABB]

    НКУ с устройствами ограничения воздействия внутренней дуги (активная защита)

    Для решения этой задачи используются совершенно другие, отличающиеся от ранее рассмотренных, принципы, заключающиеся в том, что противодействие внутренней дуге обеспечивается применением устройств, ограничивающих саму дугу.

    Существует два типа решения проблемы в этом направлении:
    • ограничение разрушающего воздействия дуги после того, как ее обнаружат специальные устройства
    • ограничение разрушающего воздействия дуги после того, как специальные устройства обнаружат возникновение избыточного давления.

    В первом случае в НКУ устанавливают устройства обнаружения дуги, реагирующие на световой поток, сопровождающий явление электрической дуги.

    При обнаружении дуги данные устройства посылают сигнал управления на размыкание вводного автоматического выключателя. Гарантируемое время реакции составляет 1-2 мс, что меньше времени срабатывания автоматического выключателя.

    Логика работы устройства обнаружения дуги следующая: Дуга, возникшая внутри НКУ, обнаруживается датчиком, реагирующим на интенсивное световое излучение, которым сопровождается горение дуги.

    Обнаружив дугу, система управления посылает сигнал автоматическому выключателю.

    Время срабатывания датчика и системы управления составляет несколько миллисекунд, что меньше времени срабатывания автоматического выключателя, осуществляющего защиту от сверхтока, который обычно для обеспечения требуемой селективности срабатывает с задержкой.

    На рис. 1 показаны места возможной установки устройства защиты внутри НКУ.

    Идеальным решением является установка, по крайней мере, одного устройства защиты в каждый шкаф многошкафного НКУ.

    Это позволит до минимума сократить длину оптоволоконных кабелей передачи сигнала.

    Для предотвращения ложного срабатывания от других источников света (т. е. не от дуги), например, таких как лампы, солнечное излучение и т. п., дополнительно в главной цепи вводного автоматического выключателя устанавливают датчик тока.

    Только при наличии двух событий, а именно: срабатывания датчика света и обнаружения аномального увеличения тока, система управления считает, что возникла электрическая дуга и подает команду на отключение вводного автоматического выключателя.

    Второе решение заключается в установке внутри НКУ датчика избыточного давления.

    Как было описано ранее, одним из характерных проявлений электрической дуги, возникшей внутри НКУ, является ударная волна.

    Это означает, что можно установить несколько датчиков давления, задачей которых является обнаружение импульса давления (с задержкой 10…15 мс), обусловленного зажиганием дуги.

    Сигнал от датчиков давления поступает на вводной автоматический выключатель, который срабатывает без задержки на обеспечение селективности.

    Такая система не нуждается в электронном устройстве обработки информации, поскольку воздействует непосредственно на независимый расцепитель автоматического выключателя.

    Вполне понятно, что такое устройство имеет фиксированный порог срабатывания.

    Датчик-реле дуги сработает, как только будет достигнуто заданное значение избыточного давления.

    Следует иметь в виду, что не так легко заранее определить значение избыточного давления, которое будет создано при зажигании дуги внутри НКУ.

    [Перевод Интент]

    Тематики

    • НКУ (шкафы, пульты,...)

    EN

    Русско-английский словарь нормативно-технической терминологии > НКУ с устройствами ограничения воздействия внутренней дуги

  • 3 действие электрической дуги, возникающей внутри НКУ распределения и управления

    1. effects of the electric arc inside switchgear and controlgear assemblу

     

    действие электрической дуги, возникающей внутри НКУ распределения и управления
    -
    [Интент]

    Параллельные тексты EN-RU

    Effects of the electric arc inside switchgear and controlgear assemblies

    In the proximity of the main boards, i.e. in the proximity of big electrical machines, such as transformers or generators, the short-circuit power is high and consequently also the energy associated with the electrical arc due to a fault is high.

    Without going into complex mathematical descriptions of this phenomenon, the first instants of arc formation inside a cubicle can be schematized in 4 phases:

    1. compression phase: in this phase the volume of the air where the arc develops is overheated owing to the continuous release of energy; due to convection and radiation the remaining volume of air inside the cubicle warms up; initially there are temperature and pressure values different from one zone to another;

    2. expansion phase: from the first instants of internal pressure increase a hole is formed through which the overheated air begins to go out. In this phase the pressure reaches its maximum value and starts to decrease owing to the release of hot air;

    3. emission phase: in this phase, due to the continuous contribution of energy by the arc, nearly all the air is forced out under a soft and almost constant overpressure;

    4. thermal phase: after the expulsion of the air, the temperature inside the switchgear reaches almost that of the electrical arc, thus beginning this final phase which lasts till the arc is quenched, when all the metals and the insulating materials coming into contact undergo erosion with production of gases, fumes and molten material particles.

    Should the electrical arc occur in open configurations, some of the described phases could not be present or could have less effect; however, there shall be a pressure wave and a rise in the temperature of the zones surrounding the arc.

    Being in the proximity of an electrical arc is quite dangerous; here are some data to understand how dangerous it is:

    • pressure: at a distance of 60 cm from an electrical arc associated with a 20 kA arcing fault a person can be subject to a force of 225 kg; moreover, the sudden pressure wave may cause permanent injuries to the eardrum;
    • arc temperatures: about 7000-8000 °C;
    • sound: electrical arc sound levels can reach 160 db, a shotgun blast only 130 db.

    [ABB]

    Действие электрической дуги, возникающей внутри НКУ распределения и управления

    Короткое замыкание вблизи больших силовых устройств, таких как трансформаторы или генераторы имеет очень большую мощность. Поэтому энергия электрической дуги, возникшей в результате короткого замыкания, очень большая.

    Не вдаваясь в сложное математическое описание данного явления, можно сказать, что первые мгновения формирования дуги внутри шкафа можно упрощенно разделить на четыре этапа:

    1. Этап сжатия: на этом этапе объем воздуха, в котором происходит зарождение дуги перегревается вследствие непрерывного высвобождения энергии. За счет конвекции и излучения оставшийся объем воздуха внутри шкафа нагревается. На этом начальном этапе значения температуры и давления воздуха в разных зонах НКУ разные.

    2. Этап расширения: с первых мгновений внутреннее давление создает канал, через который начинается движение перегретого воздуха. На этом этапе давление достигает своего максимального значения, после чего начинает уменьшаться вследствие выхода горячего воздуха.

    3. Этап эмиссии: на этом этапе вследствие непрерывного пополнения энергией дуги почти весь воздух выталкивается под действием мягкого и почти постоянного избыточного давления.

    4. Термический этап: после выхлопа воздуха температура внутри НКУ почти достигает температуры электрической дуги. Так начинается заключительный этап, который длится до тех пор, пока дуга не погаснет. При этом все металлические и изоляционные материалы, вступившие в контакт с дугой, оказываются подвергнутыми эрозии с выделением газов, дыма и частиц расплавленного материала.

    Если электрическая дуга возникнет в открытом НКУ, то некоторые из описанных этапов могут не присутствовать или могут иметь меньшее воздействие. Тем не менее будет иметь место воздушная волна и подъем температуры вблизи дуги.

    Находиться вблизи электрической дуги довольно опасно. Ниже приведены некоторые сведения, помогающие осознать эту опасность:

    • давление: На расстоянии 60 см от электрической дуги, вызванной током короткого замыкания 20 кА, человек может подвергнуться воздействию силы 225 кг. Более того, резкая волна давления может нанести тяжелую травму барабанным перепонкам;
    • температура дуги: около 7000-8000 °C;
    • шумовое воздействие: Уровень шумового воздействия электрической дуги может достигнуть 160 дБ (выстрел из дробовика – 130 дБ).

    [Перевод Интент]

    Тематики

    • НКУ (шкафы, пульты,...)

    EN

    Русско-английский словарь нормативно-технической терминологии > действие электрической дуги, возникающей внутри НКУ распределения и управления

См. также в других словарях:

  • Electric arc — An electric arc is an electrical breakdown of a gas which produces an ongoing plasma discharge, resulting from a current flowing through normally nonconductive media such as air. A synonym is arc discharge. The phenomenon was first described by… …   Wikipedia

  • НКУ с устройствами ограничения воздействия внутренней дуги — [Интент] Параллельные тексты EN RU Assemblies equipped with devices limiting internal arc effects (active protection) A design philosophy which is completely different from that just considered consists in guaranteeing the resistance to internal… …   Справочник технического переводчика

  • Hypertherm Plasma Cutting — is an American corporation which designs and manufactures metal cutting systems for use in a variety of industries such as shipbuilding, manufacturing, and automotive repair. It makes handheld and mechanized plasma cutters and consumables, as… …   Wikipedia

  • Ball lightning — is an atmospheric electrical phenomenon, the physical nature of which is still controversial. The term refers to reports of luminous, usually spherical objects which vary from pea sized to several meters in diameter. It is sometimes associated… …   Wikipedia

  • electromagnetic radiation — Physics. radiation consisting of electromagnetic waves, including radio waves, infrared, visible light, ultraviolet, x rays, and gamma rays. [1950 55] * * * Energy propagated through free space or through a material medium in the form of… …   Universalium

  • Ozone — For other uses, see Ozone (disambiguation). Ozone …   Wikipedia

  • Weather radar — in Norman, Oklahoma with rainshaft …   Wikipedia

  • Lightning — This article is about the atmospheric electrical phenomenon. For other uses, see Lightning (disambiguation). See also: Lightning strike Lightning striking Atlanta, United States Lightning is an atmospheric electrostatic discharge (spar …   Wikipedia

  • Vacuum tube — This article is about the electronic device. For experiments in an evacuated pipe, see free fall. For the transport system, see pneumatic tube. Modern vacuum tubes, mostly miniature style In electronics, a vacuum tube, electron tube (in North… …   Wikipedia

  • Capacitor — This article is about the electronic component. For the physical phenomenon, see capacitance. For an overview of various kinds of capacitors, see types of capacitor. Capacitor Modern capacitors, by a cm ruler Type Passive …   Wikipedia

  • Ferroresonance — The phenomenon of Ferroresonance is the occurrence of an unstable high voltage, typically on 3 phase electrical systems which only occurs under specific conditions. The nature of the overvoltage can cause the failure of equipment.Ferroresonance… …   Wikipedia